Rated voltage:Uo/U 300/500V
Test voltage:2000V
Insulation resistance at +20° C:≥:(+20°C):≧20MΩx km
Bending radius:
stationary :5 x cable diameterØ
flexible:10 x cable diameterØ
Temperature range:
flexible:-5°C - 80°C
stationary:-40°C - 80°C
Radiation resistance:≤80×10cJ/kg
Flame retardant:IEC 60332-1
● Stranded bare Cu conductor, extra-fine wire
● Strand structure to VDE 0295,class 6 / IEC
60228 class 6
● Core insulation: special PVC
● Black cores with printed consecutive white
number coding
● Green-yellow protective conductor
(3 cores and over) in the outer layer
● Cores twisted in layers, with optimal lay lengths
● Braided screening made of tinned copper wires
● Fabric lapping
● Outer sheath: special PVC
● Sheath colour: RAL 7001 grey
This cable is ideal for use on drag chains or as control cable for continuously moved machine components in dry and damp environments. Designed to resist up to mean mechanical bending loads.
When used for outdoor applications, adequate protection against direct exposure to sunlight must be ensured and the specified temperature limits must be observed. The tinned copper braid gives protection against electrical interference.
Part No. | No.cores Xcross-sec. mm² |
Outer Øca. mm |
Cop.weight kg / km |
Weight ca. kg / km |
---|---|---|---|---|
302051 | 5G2.5 | 13.3 | 188.0 | 386 |
302052 | 7G2.5 | 16.0 | 260.3 | 500 |
302053 | 12G2.5 | 18.0 | 405.0 | 694 |
302054 | 4G4.0 | 15.9 | 237.8 | 461 |
302055 | 5G4.0 | 17.5 | 283.4 | 552 |
302056 | 4G6.0 | 16.3 | 342.8 | 608 |
302057 | 5G6.0 | 17.9 | 410.3 | 755 |
302058 | 4G10 | 21.8 | 510.5 | 935 |
302059 | 5G10 | 23.8 | 629.7 | 1100 |
302060 | 4G16 | 24.0 | 772.0 | 1275 |
302061 | 5G16 | 27.0 | 1006.0 | 1695 |